• The LA60S-TU replaces the LA60TU/LA60TU-2 products which are now discontinued. It is a 60kW Air Source heat pump for commercial applications.
The main differences are-
• The PCO5+ controller is replaced by a more modern PCO-OEM controller and the old PGD text-based User Interface replaced with a PCO Touch screen.
• The performance of the product is slightly different to the older models, so check with Application Design to ensure suitability.
• The multi-way comms cable is no longer used. It uses a Modbus (Belden 9842 or equiv) cable for comms between indoors and outdoors plus 230v mains link indoors to outdoors and 400v 3-phase power outdoors for the compressors.