What ducting can be used for Edel 200/270L?

Must comply to air connection and ducting design section on installation instructions.


It is essential to maintain a minimum air flow rate through the ducting for correct operation of the appliance. The nominal mass flow rate must be maintained above 320m3/hr. For the fan to operate in Fan speed 1, the maximum system pressure drop across the ducting connections must not exceed 100Pa and for Fan speed 2 the maximum pressure drop must not exceed 220Pa


The ducting used to connect the air intake and exhaust must be sufficiently insulated to prevent condensation forming. Condensation may result in damage to the appliance and/or building fabric. Dimplex does not take any responsibility for issues caused by poor ducting design or installation.


We don't supply the ducting but can be purchased from www.ubbink.com



Ducting must be installed in accordance with manufactures instructions.



Applicable Models

Edel - EDL200UK-630RF, EDL270UK-630RF, EDL200UK-630, EDL270UK-630



Require additional help? Please follow link below

https://glendimplexservice.freshdesk.com/a/solutions/articles/79000136321

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article