Applicable to models: LA6MI, LA9MI, LA12MI, LA16MI
Issue: Error code H70 shown on the display.
What this means: H70 error is due to the backup heater Over Load Protection device activated or disconnected.
Action: Engineer visit needed to investigate. Engineer should follow the flow diagram below.
Underlying cause is likely to be air lock or poor flow in water between heat pump & house or excessive inlet temp if OLP keeps tripping out.
Before carrying out any works, isolate the heat pump at the mains supplies!
Malfunction Decision Conditions:
During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit.
Malfunction Caused:
1 Faulty power supply connector connection.
2 Faulty connector connection.
3 Faulty indoor backup heater overload protector (OLP).
4 Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 60 seconds.
Possible parts required depending on engineers diagnosis:
• OLP thermostatic cut out switch
LA6MI / LA9MI / LA12MI / LA16MI part: X-2511030
• Main Water PCB (part number depends on model of heat pump)
LA6MI part: X-2511031
LA9MI part: X-2511039
LA12MI part: X-2511051
LA16MI part: X-2511058
Require additional help? Please follow link below
https://glendimplexservice.freshdesk.com/a/solutions/articles/79000136321
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article