I have H70 error on my LA-MI heat pump. What does this mean?


Applicable to models:  LA6MI, LA9MI, LA12MI, LA16MI

 

Issue:  Error code H70 shown on the display. 

 

What this means: H70 error is due to the backup heater Over Load Protection device activated or disconnected.


Action: Engineer visit needed to investigate. Engineer should follow the flow diagram below.

 

Underlying cause is likely to be air lock or poor flow in water between heat pump & house or excessive inlet temp if OLP keeps tripping out.


Before carrying out any works, isolate the heat pump at the mains supplies!  



Malfunction Decision Conditions:

During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit.

 

Malfunction Caused:

1 Faulty power supply connector connection.

2 Faulty connector connection.

3 Faulty indoor backup heater overload protector (OLP).

4 Faulty indoor unit PCB (main).

 

Abnormality Judgment:

Continue for 60 seconds.


 


Possible parts required depending on engineers diagnosis:

• OLP thermostatic cut out switch

LA6MI / LA9MI / LA12MI / LA16MI part: X-2511030


• Main Water PCB (part number depends on model of heat pump)

LA6MI part: X-2511031
LA9MI part: X-2511039
LA12MI part: X-2511051
LA16MI part: X-2511058


Require additional help? Please follow link below

https://glendimplexservice.freshdesk.com/a/solutions/articles/79000136321